型号
| YUOM030 HSEACQ | YUOM035 HSEACQ | YUOM045 HSEACQ | YUOM050 HSEACQ | YUOM060 HSEACQ | YUOM080 HSEACQ | YUOM09 0HSEACQ | YUOM0100 HSEACQ | YUOM0120 HSEACQ |
框体尺寸(高*宽*厚)
| mm | 840×1100×390
| 1650×1100×390 |
| 额定制冷量 | kW
| 8.0 | 10.0 | 12.5 | 14.0 | 15.5 | 22.4 | 24.5 | 28.0 | 32.0 |
| 额定制热量 | kW
| 9.5 | 11.2 | 14.0 | 16.0 | 17.0 | 25.0 | 26.0 | 31.5 | 34.0 |
| 地暖制热量 | kW
| 12.0 | 12.0 | 14.0 | 16.0 | 17.0 | 25.0 | 26.0 | 31.5 | 34.0 |
室外机 额定 功率 | 空调制冷 | kW
| 2.0 | 2.6 | 3.54 | 4.15 | 5.13 | 6.00 | 6.80 | 7.35 | 8.90 |
| EER | kW/kW
| 4.0 | 3.85 | 3.53 | 3.37 | 3.02 | 3.73 | 3.60 | 3.90 | 3.72 |
| 空调制热 | kW
| 2.30 | 2.70 | 3.30 | 4.30 | 4.83 | 6.00 | 6.40 | 8.20 | 9.40 |
| 制热 COP | kW/kW
| 4.13 | 4.14 | 4.24 | 3.72 | 3.52 | 4.17 | 4.06 | 3.82 | 3.62 |
地暖功率
| kW
| 2.70 | 2.70 | 3.20 | 3.90 | 4.50 | 5.68 | 6.20 | 7.60 | 8.40 |
| 地暖 COP | kW/kW
| 4.44 | 4.44 | 4.38 | 4.10 | 3.78 | 4.40 | 4.19 | 4.42 | 4.05 |
IPLV(c)
| 7.50 | 7.20 | 7.00 | 6.80 | 6.60 | 8.00 | 7.50 | 7.20 | 7.00 |
| APF | 5.30 | 5.25 | 5.25 | 5.20 | 4.90 | 4.90 | 4.80 | 4.80 | 4.60 |
运行噪音(制冷 /制热)
| dB(A)
| 52/56 | 53/56 | 54/56
| 55/57 | 55/57 | 57/59 | 57/59 | 58/60 | 59/61 |
室内机容量连接范围 | %
| 50~130 | 50~150 |
| 电源 | 220V ~ 50Hz | 380V ~ 3N 50Hz
|
| 压缩机品牌和形式 | 约克牌高效双转子压缩机
| 约克牌高效喷气增焓涡旋式压缩机
|
制冷运行范围
| ℃DB
| -5 ~ 52(DB)
|
制热运行范围
| ℃DB
| -20 ~ 30(DB) ( 地暖烘干温度可到 43℃)
|
注: 1、额定制冷量测试工况:室内温度:27℃DB,19℃WB 室外温度:35℃DB 管道长度:7.5m,管道高度差:0m
额定制热量测试工况:室内温度:20℃DB 室外温度:7℃DB,6℃WB 管道长度:7.5m,管道高度差:0m
2、上表中噪音数值是在无反射回声的消音室内测得。在实际安装情况下,受环境噪音及反射回声影响,一般高于此数值。
型号
| YUOM035 HSEAAQ | YUOM045 HSEAAQ | YUOM050 HSEAAQ | YUOM060 HSEABQ | YUOM060 HSEAAQ | YUOM065 HSEAAQ | YUOM070 HSEAAQ |
框体尺寸(高*宽*厚)
| mm | 1250×950×320
| 1650×950×320
|
| 额定制冷量 | kW
| 10.0 | 12.5 | 14.0 | 15.5 | 15.5 | 18.0 | 20.0 |
| 额定制热量 | kW
| 11.2 | 14.0 | 16.0 | 17.0 | 18.0 | 20.0 | 22.4 |
| 地暖制热量 | kW
| 12.0 | 14.0 | 16.0 | 17.0 | 18.0 | 20.0 | 22.4
|
制冷功率 | 2.0 | 2.50 | 3.35 | 3.99 | 4.60 | 4.43 | 5.10 | 5.69 |
| EER | kW/kW
| 4.00 | 3.73 | 3.57 | 3.37 | 3.50 | 3.53 | 3.51 |
| 制热功率 | kW
| 2.63 | 3.40 | 3.95 | 4.30 | 4.40 | 5.00 | 5.60 |
| 空调 COP | kW/kW
| 4.26 | 4.12 | 4.05 | 3.95 | 4.09 | 4.00 | 4.00 |
| 地暖功率 | kW
| 2.53 | 3.22 | 3.58 | 4.20 | 4.15 | 4.80 | 5.40 |
| 地暖 COP | kW/kW
| 4.43 | 4.35 | 4.47 | 4.05 | 4.34 | 4.17 | 4.15 |
| APF | 5.30 | 5.25 | 5.20 | 4.90 | 5.10 | 5.05 | 5.00 |
| IPLV(c) | 7.40 | 7.10 | 7.00 | 6.80 | 7.30 | 7.10
| 7.00 |
| 配比率 | 50~150%
| 50~130% | 50~150% |
| 电源 | 220V ~ 50Hz |
| 压缩机品牌和形式 | 约克牌高效喷气增焓双转子压缩机
| 约克牌高效喷气增焓涡旋式压缩机
|
制冷运行范围
| ℃DB
| -5~52℃
|
制热运行范围
| ℃DB
| -20~30℃
|
注: 1、额定制冷量测试工况:室内温度:27℃DB,19℃WB 室外温度:35℃DB 管道长度:7.5m,管道高度差:0m
额定制热量测试工况:室内温度:20℃DB 室外温度:7℃DB,6℃WB 管道长度:7.5m,管道高度差:0m
2、上表中噪音数值是在无反射回声的消音室内测得。在实际安装情况下,受环境噪音及反射回声影响,一般高于此数值。